Merlin Gas Detector i

  • 24VAC or DC Powered
  • Traffic Light Indication
  • Built-In Audible Alarm
  • Three Alarm Relay Outputs
  • 0-10VDC Variable Output
  • BMS standalone compatibility
  • Various gas detector types available
  • End of Life Reminder
  • Covered by S&S Northern Ltd 3 year warranty.

Description

The i range of gas detectors are used in various applications such as boiler/plant rooms, hospitals, laboratories and high rise buildings. These sensors are specifically built to work with all Merlin control panels and can also be used direct with BMS control panels. The traffic light indicator will summarise the gas levels. Green = safe | Yellow = Attention | Red = Danger.

DETECTOR i SPECIFICATION
GENERAL MECHANICAL
Model Detector i Size (H x W x D) 5.95 x 4.37 x 1.97” (151 x 111 x 50mm)
Target Gas CO, CO2, LPG, NG, H2S Housing Material ABS PA765. Flame Retardant UL 94V-1
Mounting Safe Zone – Indoor use – Wall Mounted Weight 212g
USER INTERFACE POWER & RELAYS
Display N/A Rated Power 0.6W Max
Screen Brightness N/A Rated Voltage 12-24Vdc or 24Vac
Visual Indicators Power (Green), Low Alarm (Yellow), High Alarm (Red), EOL (Yellow) Volt Free Relay 1A switching current @ 24V AC/DC
Audible Alarm >65dB @ 3.28ft (1m). Quiet conditions.    
Language English    
ENVIRONMENTAL WIRING & COMPLIANCE
Ingress Protection (IP) Not Formally Evaluated Wiring Typical Min. 2.5mm² / 75°C min / Tinned copper
Operating -10 ~ 50°C / 20 ~ 90% RH (non-condensing) Electrical Safety & EMC CE / UKCA, BS EN 61010-1:2010 +A1:2019, BS EN 50270
Storage 0 ~ 50°C / 30 – 80% RH (no condensation) Altitude Rating 2000m